4 Data Structures
4.1 Operating Modes
The GSD file contains 3 operating modes, supporting data I/O structures as follows:
Data structure Basic mode Extended mode Parameter upload/download mode
Soft Starter Control I/O Data Structure
Soft Starter Monitoring I/O Data Structure
Soft Starter Programming I/O Data Structure
The basic mode allows starting and stopping the soft starter and reading limited information on operating status.
The extended mode defines more bytes allowing to read soft starter operating data such as actual motor current and motor
temperature.
The parameter upload/download mode allows reading and writing soft starter parameter values.
4.2 Soft Starter Control I/O Data Structure
Table 2: Master/Slave Control Word Structure
Byte Bits Details
0 0–1 Reserved
2–3 0=Use soft starter remote input to select motor set
1=Use primary motor set when starting
2=Use secondary motor set when starting
4=Reserved
4 0=Stop action is a soft stop (as selected on the soft starter)
1=Stop action is a quick stop (coast to stop)
5–7 Reserved
1 0 0=Stop
1=Start
1–2 Reserved
3 1=Reset
4–7 Reserved
NOTICE
Bit 4 of byte 0 must be set to 0 for the soft starter to start.
Data Structures
Installation Guide | PROFIBUS Card
AQ277154583779en-000101 / 175R1181
8 | Danfoss A/S © 2018.09