TP7001
26
GB
Option 12
Optimum Start Control / Delayed Start Maximum
Activation Time Setting (Option 11 set to 1 or 2)
This feature allows the maximum optimum or delayed
start time to be set. Press the + button until Option
12 is displayed, use the Λ or V buttons to select
required setting (only active if Option 11 is set to 1
or 2). The maximum time must be adjusted to match
the building energy characteristics. Use the Λ or V
buttons to select the required period.
Optimum Start
If the building fails to reach temperature on time, increase the setting
by 15 minute steps each day until the correct setting is found. If the
building reaches temperature ahead of time, decrease the setting
by 15 minute steps each day until the correct setting is found.
15 mins, warm air systems, well insulated building.
30 mins, warm air systems, well insulated building.
45 mins, warm air system poorly insulated building.
60 mins, radiator system, light weight well insulated building.
(Factory setting)
75 mins, radiator system, light weight medium insulation.
90 mins, radiator system, medium weight poorly insulation.
105 mins, radiator system, heavy weight building, well insulated.
120 mins, radiator system, heavy weight building, poorly insulated.
Delayed Start
For Delayed Start, if the building fails to reach temperature quickly
enough, decrease the setting by 15 minutes, if the building reaches
temperature too quickly, increase the setting by 15 minutes.
120 mins, warm air systems, well insulated building.
105 mins, warm air systems, well insulated building.
90 mins, warm air system poorly insulated building.
75 mins, radiator system, light weight well insulated building.
60 mins, radiator system, light weight medium insulation.
(Factory Setting)
45 mins, radiator system, medium weight poorly insulation.
30 mins, radiator system, heavy weight building, well insulated.
15 mins, radiator system, heavy weight building, poorly insulated.