TP9000
10
Option 34 - Select On/Off or Chrono-proportional
This allows the thermostat to be set to run in On/Off
mode or for a chrono-proportional cycle rate to be
selected. Press + until Option 34 is displayed, use V
and Λ to select required setting.
0 On/Off
3 3 cycles per hour
6 6 cycles per hour (factory setting)
9 9 cycles per hour
12 12 cycles per hour
Option 35 - Set integration time (Option 34 set to 3, 6, 9 or 12)
(seek advice prior to adjusting)
This adjusts the integration time of the PI algorithm
to increase control accuracy. It is only active if
option 34 has been set to Chrono 3, 6, 9 or 12.
It should only be adjusted after seeking advice
from the manufacturer. Press + until Option 35 is
displayed, use
V and Λ to select required setting.
2.5 Integration time set to 2.5% (factory setting)
5 Integration time set to 5%
10 Integration time set to 10%
Option 36 - Set temperature override rule
This establishes the degree of temperature override
available to the user. Press + until Option 36 is
displayed, use
V and Λ to select required setting.
Setting 0 No limit (factory setting)
Setting 1 Limited to ±2°C
Setting 2 No override allowed

Table of Contents

Other manuals for Danfoss TP9000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss TP9000 and is the answer not in the manual?

Danfoss TP9000 Specifications

General IconGeneral
BrandDanfoss
ModelTP9000
CategoryThermostat
LanguageEnglish

Related product manuals