How to size your VLT
Technical data
Mains: 1
××
××
× 220/230/240 V, 3
××
××
× 208/220/230/240 V 3 x 208/220/230/240 V
Meets the international standards, UL/ cUL
4
) VLT type 2010 2015 2020 2030 2040 2050
Constant load (CT):
Output current I
VLT.N
[A] 2.2 3.1 4.0 7.5 10.6 16.7
I
VLT.MAX
[A] (60 s) 3.5 4.9 6.3 10.5 17.0 26.7
Output S
VLT.N
[kVA] 0.9 1.3 1.6 3.1 4.4 6.9
S
VLT.MAX
[kVA] (60 s) 1.4 2.1 2.6 4.3 7.0 11.0
Typical shaft output P
VLT.N
[kW] 0.37 0.55 0.75 1.5 2.2 3.0
Max. cable cross section [mm
2
] 44 4444
Max. motor cable length [m] 40 (with motor coils IP 10:
unscreened cables 300 m, screened cables 150 m)
Output voltage U
M
[%] 0-100% of mains voltage
Output frequency f
M
[Hz] 0-120 or 0-500; programmable
Rated motor voltage U
M,N
[V] 200/208/220/230/240
Rated motor frequency f
M,N
[Hz] 50/60/87/100
Thermal motor protection during operation Built-in thermal motor protection (electronic)
Switching on the output Unlimited (frequent switching may cause cut-out)
Ramp times [s] 0.1-800
VLT type 2010 2015 2020 2030 2040 2050
Max. input current I
L,N
[A] (5.3/3.5) (8.5/5.6) (10.6/7.1) (18/12) (-/10) (-/16)
Max. cable cross section [mm
2
] 44 4444
Max. prefuses [A] 10 16 20 20 20 25
Bussmann Fuse type KTN-R 250 V AC
5
) [A] 10 15 20 20 20 25
Mains supply voltage [V] 1 x 220/230/240 ±10 % 3 x 208/220/
3 × 208/220/230/240 ±10 % 230/240±10 %
Mains supply frequency [Hz] 50/60
Power factor/cos. ϕ
1
Without mains filter:0.50/0.87 0.90/1.0 0.90/1.0
With mains filter:0.65/1.0
Efficiency >0.94 at rated load
Switching on the input times/min. 5
VLT type 2010 2015 2020 2030 2040 2050
Weight [kg] IP 20 2.0 2.0 2.1 2.1 4.6 4.6
Weight [kg] with built-in RFI filter IP 20 3.7 3.7 3.8 3.8
Power loss at max. load CT [W] 39 53 69 126 136 236
Enclosure IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
Vibration test [g] 0.7
Relative humidity [%] Max. 95 IEC 721 (according to VDE 0160)
Ambient temperature [°C] 0 → +40 at full-load operation
2
)
(according to VDE 0160) [°C] −25 → +70, storage/transport
Frequency converter protection Grounding and short-circuit proof
3
)
EMC applied standards Emission EN 55011, Group 1, Class A,
(see page 90) CISPR 11 (with RFI and motor filter)
Immunity IEC 1000-4
UL file-number E134261
2
) In the range -10 - 0 °C the unit can start and run, but the display indications and certain operating characteristics
will not meet the specifications.
3
) Brake option without protection
4
) Units with built-in RFI filter are not UL-approved.
5
) For the North American market
■