27MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Mains supply 3 x 440/460/500 V Technical data
According to international VDE and UL/CSA requirements VLT type 3060 3075 3100 3125 3150 3200 3250
Constant torque (CT):
Output current I
VLT,N
[A] 77 96 124 156 180 240 302
I
VLT,MAX
[A](60s) 116 144 186 234 270 360 453
Output S
VLT,N
[kVA] 67 83 107 135 156 208 262
S
VLT,MAX
(60s) [kVA] 100 125 161 203 234 312 392
Typical shaft output P
VLT,N
[kW] 55 75 90 110 132 160 200
Quadratic torque (VT):
Output current I
VLT,N
[A] 96 124 156 180 240 302 361
I
VLT,MAX
[A](60s) 106 136 172 198 264 332 397
Output S
VLT,N
[kVA] 83 107 135 156 208 262 313
Typical shaft output P
VLT,N
[kW] 75 90 110 132 160 200 250
Max. cable cross-section [mm
2
] 70 70 150 150 150 2 x 95 2 x 95
Max. motor cable length [m] 300
Output voltage U
M
[%] 0-100 of mains voltage
Output frequency f
M
[Hz] 0-120 or 0-500; programmable
Rated motor voltage U
M,N
[V] 380/400/415/440/460/500
Rated motor frequency f
M,N
[Hz] 50/60/87/100
Thermal protection during operation Integrated thermal motor protection (electronic); thermistor
to DIN 44081
Switching on output Unlimited (frequent switching on output may result in fault message)
Ramp times [s] 0.1 - 3600
VLT type 3060 3075 3100 3125 3150 3200 3250
Input current I
L,N
[A] 75.8 94.4 123.4 155.3 177.1 238.9 307.6
I
L,MAX
(60s)[A] 113.7 141.6 185.1 233.0 265.7 358.4 461.4
Quadratic load I
L,N
[A] 94.4 123.4 155.3 177.1 238.9 307.6 359.3
I
L,MAX
(60s)[A] 106.0 136.0 172.0 198.0 264.0 332.0 397.0
Max. cable cross-section [mm2] 120.0 120.0 2 x 120 2 x 120 2 x 120 2 x 240 2 x 240
Max. pre-fuses
1)
[A] 150.0 150.0 250.0 250.0 300.0 450.0 500.0
Supply voltage (VDE 0160) [V] 3 x 380/400/415/440/460/500 ±10%
Supply frequency [Hz] 50/60
Power factor / cos. ϕ
1
0.9/1.0
Efficiency 0.96 at 100% load
Switching on input times/min. 1
VLT type 3060 3075 3100 3125 3150 3200 3250
Weight (kg)
IP 21 147 147 211 211 220 306 306
IP 54 147 147 211 211 220 306 306
Power loss at max. load CT [W]
Front 423 529 713 910 1091 1503 1812
Heat sink 859 1074 1447 1847 2216 3051 3679
Power loss at max. load VT [W]
Front 529 713 910 1091 1503 1812 2209
Heat sink 1074 1447 1847 2216 3051 3679 4485
Enclosure IP 21 / IP 54, NEMA 1/12
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
Ambient temperature [°C] -10→ +40 at full load
2)
(VT) -10→ +45 (CT)
2)
(to VDE 0160) [°C] -30/25→ +65/70 in storage/transport
Frequency converter protection Jord- og kortslutningssikker
EMC standards Emission EN 55011, EN 55014
(See section “EMC test results”) Immunitet EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
IEC 1000-4-5 VDE 0160
1) Bussman rapid type JJS integrated.
2) In the range -10 to 0°C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the
specifications.