EasyManuals Logo
Home>Danfoss>DC Drives>VLT 5000 Series

Danfoss VLT 5000 Series Operating Instructions

Danfoss VLT 5000 Series
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #112 background imageLoading...
Page #112 background image
VLT
®
5000 Series
Programming
VLT 5122-5552, 380-500 V and VLT 5042-5602,
525-690 V work with a reduced DC current rated
as 80% of I
VLT,N
at 110% overload.
125 DC braking current
(DC BRAKE CURRENT)
Value:
50 %
Function:
This parameter is used for setting the DC brake
current that is activated upon a stop when the DC
brake frequency set in parameter 127 has been
reached, or if the DC brake inverse is active via digital
terminal 27 or via a serial communication port. The
DC braking current will be active for the duration of
the DC braking time set in parameter 126.
NB!:
The maximum value depends on the rated
motor current. If the DC braking current
is active, the frequency converter has a
switching frequency of 4.5 kHz.
Description of choice:
To be set as a percentage value of the rated motor
current I
M,N
set in parameter 105.
100% DC braking current corresponds to I
M,N
.
Warning: 100 % supply for too long
may damage the motor.
VLT 5122-5552, 380-500 V and VLT 5042-5602,
525-690 V work with a reduced DC current rated
as 80% of I
VLT,N
at 110% overload.
126 DC braking time
(DC BRAKING TIME)
Value:
0.0 (OFF) - 60.0 sec.
10.0 sec.
Function:
This parameter is for setting the DC braking time
for which the DC braking current (parameter
125) is to be active.
Description of choice:
Set the desired time.
127 DC brake cut-in frequency
(DC BRAKE CUT-IN)
Value:
0.0 - parameter 202
0.0 Hz (OFF)
Function:
This parameter is for setting the DC brake cut-in
frequency at which the DC braking current (parameter
125) is to be active, in connection with a stop command.
Description of choice:
Set the desired frequency.
128 Motor thermal protection
(MOT.THERM PROTEC)
Value:
No protection (NO PROTECTION)
[0]
Thermistor warning (THERMISTOR WARN)
[1]
Thermistor trip (THERMISTOR TRIP)
[2]
ETR Warning 1 (ETR WARNING1)
[3]
ETR Trip 1 (ETR TRIP1)
[4]
ETR Warning 2 (ETR WARNING2)
[5]
ETR Trip 2 (ETR TRIP2)
[6]
ETR Warning 3 (ETR WARNING3)
[7]
ETR Trip 3 (ETR TRIP3)
[8]
ETR Warning 4 (ETR WARNING 4)
[9]
ETR Trip 4 (ETR TRIP4)
[10]
Function:
The frequency converter is able to monitor the motor
temperature in two different ways:
- Via a thermistor sensor connected to one
of the analogue inputs, terminals 53 and 54
(parameters 308 and 311).
- Calculation of the thermal load, based on the
current load and the time. This is compared with
the rated motor current I
M,N
andtheratedmotor
frequency f
M,N
. The calculations made take into
account the need for a lower load at lower speeds
because of less cooling from the fan.
ETR functions 1-4 do not start calculating the load
until there is a switch-over to the Setup in which
they were selected. This enables the use of the
ETR function, even where two or several motors
alternate. For the North American market: The ETR
functions provide class 10 or 20 motor overload
protection in accordance with NEC.
Description of choice:
Select No protection if no warning or tripping is
required when the motor is overloaded.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
111

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals