VLT
®
5000 Series
Preset reference, lsb and Preset reference, msb
enables a choice of one of the four preset references,
in accordance with the table below.
Preset ref. msb Preset ref. lsb
Preset ref. 1 0 0
Preset ref. 2 0 1
Preset ref. 3 1 0
Preset ref. 4 1 1
Freeze reference - freezes the actual reference. The
frozen reference is now the point of enable/condition
for Speed up and Speed down to be used.
If speed up/down is used, the speed change
always follows ramp 2 (parameters 209/210)
in the range 0 - Ref
MAX
.
Freeze output - freezes the actual motor
frequency (Hz). The frozen motor frequency is
now the point of enable/condition for Speed up
and Speed down to be used.
If speed up/down is used, the speed change
always follows ramp 2 (parameters 209/210)
in the range 0 - f
M,N
.
NB!:
If Freeze output is active, the frequency
converter cannot be stopped via terminals
18 and 19, but only via terminal 27 (to
be programmed for Coasting stop, inverse [0] or
Reset and coasting stop, inverse [1]).
After Freeze output, the PID integrators are reset.
Speed up and Speed down are selected if digital
control of the up/down speed is desired (motor
potentiometer). This function is only active if Freeze
reference or Freeze output has been selected. As long
as there is a logic ‘1‘ on the terminal selected for speed
up, the reference or the output frequency will increase.
Follow ramp 2 (parameter 209) in the range 0 - f
MIN
.
As long as there is a logic ‘1‘ on the terminal
selected for speed down, the reference or the
output frequency will be reduced. Follow ramp 2
(parameter 210) in the range 0 - f
MIN
.
Pulses (logic ‘1‘ minimum high for 3 ms and a minimum
pause of 3 ms) will lead to a change of speed of 0.1%
(reference) or 0.1 Hz (output frequency).
Example:
Ter minal Fre eze ref./
(16) (17) Freeze output
No speed change 0 0 1
Speed down 0 1 1
Speed up 1 0 1
Speed down 1 1 1
The speed reference frozen via the control panel
can be changed even if the frequency converter has
stopped. The frozen reference will be remembered
in case of a mains drop-out.
Selection of Setup, lsb and Selection of Setup,
msb enables a choice of one of the four Setups;
however, this presupposes that parameter 004
has been set at Multi Setup.
Selection of Setup, msb/Speed up and Selection
of Setup, lsb/Speed down - together with
the use of Freeze reference or Freeze output -
enable up/down speed change.
The selection of Setup occurs in accordance
with the below verification table:
Selection of Setup Freeze ref/
(32)msb (33)lsb Freeze output
Setup 1 0 0 0
Setup 2 0 1 0
Setup 3 1 0 0
Setup 4 1 1 0
No speed change 0 0 1
Speed down 0 1 1
Speed up 1 0 1
Speed down 1 1 1
Catch-up/Slow-down is selected if the reference
value is to be increased or reduced by a programmable
percentage value set in parameter 219.
Slow-down Catch-up
Unchanged speed 0 0
Reduced by %-value 1 0
Increased by %-value 0 1
Reduced by %-value 1 1
Ramp 2 is selected if a change between ramp 1
(parameters 207-208) and ramp 2 (209-210) is desired.
Logic 0 leads to ramp 1, while logic 1 leads to ramp 2.
Mains failure inverted is to be selected if parameter
407 Mains failure and/or parameter 408 Quick
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
124

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals