VLT
®
5000 Series
Programming
Description of choice:
Set the desired time.
318 Function after time out
(LIVE ZERO FUNCT.)
Value:
✭Off (OFF)
[0]
Freeze output frequency (FREEZE OUTPUT FREQ.)
[1]
Stop (STOP)
[2]
Jog (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter allows a choice of the function to
be activated if the input signal on terminal 60 drops
below 2 mA, provided parameter 315 has been set
higher than 2 mA and that the preset time for time-out
(parameter 317) has been exceeded.
If more time-outs occur at the same time the
frequency converter will give the following priority
to the time-out function:
1. Parameter 318 Function after time out
2. Parameter 346 Function after encoder loss
3. Parameter 514 Bus time interval function
Description of choice:
The output frequency of the frequency converter can be:
- frozen at the present value
- overruled to stop
- overruled to jog frequency
- overruled to max. frequency
- overruled to stop with subsequent trip.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
129