VLT
®
5000 Series
â– Compact, Mains supply 3 x 200 - 240 V
According to international requirements VLT type 5008 5011 5016 5022 5027
Normal overload torque (110 %):
Output current I
VLT,N
[A] 324661.27388
I
VLT, MAX
(60
s) [A]
35.2 50.6 67.3 80.3 96.8
Output (240 V) S
VLT,N
[kVA] 13.3 19.1 25.4 30.3 36.6
Typical s haft o utpu t P
VLT,N
[kW] 7.5 11 15 18.5 22
Typical s haft o utpu t P
VLT,N
[HP] 10 15 20 25 30
High overload torque (160 %):
Output current I
VLT,N
[A] 25324661.273
I
VLT, MAX
(60
s) [A]
40 51.2 73.6 97.9 116.8
Output (240 V) S
VLT,N
[kVA] 1013192530
Typical s haft o utpu t P
VLT,N
[kW] 5.5 7.5 11 15 18.5
Typical s haft o utpu t P
VLT,N
[HP] 7.5 10 15 20 25
Max. cable cross-section to motor, IP 54 16/6 16/6 35/2 35/2 50/0
brake and loadsharing [mm
2
/AWG]
2)5)
IP 20 16/6 35/2 35/2 35/2 50/0
Min. cable cross-section to motor, brake
and loadsharing
4)
[mm
2
/AWG]
2)
10/8 10/8 10/8 10/8 16/6
Rated input current (200 V) I
L,N
[A] 3246617388
Max. cable cross-section, IP 54 16/6 16/6 35/2 35/2 50/0
power [mm
2
]/[AWG]
2)5)
IP 20 16/6 35/2 35/2 35/2 50/0
Max. pre-fuses [-]/UL
1)
[A] 50 60 80 125 125
Efficiency
3)
0.95 0.95 0.95 0.95 0.95
Weight IP 20 EB [kg] 21 25 27 34 36
Weight IP 54 [kg] 38 40 53 55 56
Power loss at max. load.
- high overload torque
(160 %)
[W]
340 426 626 833 994
- normal overload torque
(110 %)
[W]
426 545 783 1042 1243
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply
with IP 20. Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
MG.51.A9.02 - VLT is a registered Danfoss trademark
18