Installation of VLT 5001-5602
All frequency converters must be installed in a
way that ensures proper cooling.
Cooling
All Bookstyle and Compact units require a minimum
space above and below the enclosure.
Side by side/flange by flange
All frequency converters can be mounted side
by side/flange by flange.
d [mm] Comments
Bookstyle
VLT 5001-5006, 200-240 V 100
VLT 5001-5011, 380-500 V 100
Installation on a plane, vertical surface (no spacers)
Compact (all enclosure types)
VLT 5001-5006, 200-240 V 100
VLT 5001-5011, 380-500 V 100
VLT 5001-5011, 525-600 V 100
Installation on a plane, vertical surface (no spacers)
VLT 5008-5027, 200-240 V 200
VLT 5016-5062, 380-500 V 200
VLT 5072-5102, 380-500 V 225
VLT 5016-5062, 525-600 V 200
Installation on a plane, vertical surface (no spacers)
VLT 5032-5052, 200-240 V 225
VLT 5122-5302, 380-500 V 225
VLT 5042-5352, 525-690 V 225
Installation on a plane, vertical surface (no spacers)
IP 54 filter mats must be changed when they are dirty.
VLT 5352-5552, 380-500 V 225
VLT 5402-5602, 525-690 V 225
IP 00 above and below enclosure
IP 21/IP 54 only above enclosure
MG.51.A9.02 - VLT is a registered Danfoss trademark
41

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals