VLT
®
5000 Series
Application
configuration
■ Two-wire transmitter
Parameter 314 = Reference [1], Feedback [2]
Parameter 315 = Terminal 60, min. scaling
Parameter 316 = Terminal 60, max. scaling
■ Current reference with speed feedback
Parameter 100 = Speed control, closed loop
Parameter 308 = Feedback [2]
Parameter 309 = Terminal 53, min. scaling
Parameter 310 = Terminal 53, max. scaling
Parameter 314 = Reference [1]
Parameter 315 = Terminal 60, min. scaling
Parameter 316 = Terminal 60, max. scaling
■ Encoder connection
Parameter 306 = Encoder input B [24]
Parameter 307 = Encoder input A [25]
If an encoder is connected that only has one
output to Encoder input A [25], Encoder input B
[24] must be set to No function [0].
MG.51.A9.02 - VLT is a registered Danfoss trademark
75