EasyManuals Logo
Home>Danfoss>DC Drives>VLT 5032

Danfoss VLT 5032 User Manual

Danfoss VLT 5032
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
Bookstyle and Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5005 5006 5008 5011
Output current
I
VLT,N
[A] (380-440 V)
7.2 10 13 16
I
VLT, MAX
(60 s) [A] (380-440 V)
11.5 16 20.8 25.6
I
VLT,N
[A] (441-500 V)
6.3 8.2 11 14.5
I
VLT, MAX
(60 s) [A] (441-500 V)
10.1 13.1 17.6 23.2
Output S
VLT,N
[kVA] (380-440 V)
5.5 7.6 9.9 12.2
S
VLT,N
[kVA] (441-500 V)
5.5 7.1 9.5 12.6
Typical shaft output
P
VLT,N
[kW]
3.0 4.0 5.5 7.5
Typical shaft output
P
VLT,N
[HP]
4 5 7.5 10
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10
4/10 4/10 4/10
Rated input current
I
L,N
[A] (380 V)
7 9.1 12.2 15.0
I
L,N
[A] (460 V)
6 8.3 10.6 14.0
Max. cable cross-section power [mm
2
]/[AWG]
2)
4/10 4/10 4/10 4/10
Max. pre-fuses [-]/UL
1)
[A]
16/15 25/20 25/25 35/30
Efficiency
3)
0.96 0.96 0.96 0.96
Weight IP 20 EB Bookstyle [kg] 7.5 9.5 9.5 9.5
Weight IP 20 EB Compact [kg] 8.5 10.5 10.5 10.5
Weight IP 54 EB Compact [kg] 12 14 14 14
Power loss at max. load. [W] 139 198 250 295
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 17
Technical data

Table of Contents

Other manuals for Danfoss VLT 5032

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5032 and is the answer not in the manual?

Danfoss VLT 5032 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5032
CategoryDC Drives
LanguageEnglish

Related product manuals