Bookstyle and Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5001 5002 5003 5004
Output current
I
VLT,N
[A] (380-440 V)
2.2 2.8 4.1 5.6
I
VLT, MAX
(60 s) [A] (380-440 V)
3.5 4.5 6.5 9
I
VLT,N
[A] (441-500 V)
1.9 2.6 3.4 4.8
I
VLT, MAX
(60 s) [A] (441-500 V)
3 4.2 5.5 7.7
Output
S
VLT,N
[kVA] (380-440 V)
1.7 2.1 3.1 4.3
S
VLT,N
[kVA] (441-500 V)
1.6 2.3 2.9 4.2
Typical shaft output
P
VLT,N
[kW]
0.75 1.1 1.5 2.2
Typical shaft output
P
VLT,N
[HP]
1 1.5 2 3
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10
4/10 4/10 4/10
Rated input current
I
L,N
[A] (380 V)
2.3 2.6 3.8 5.3
I
L,N
[A] (460 V)
1.9 2.5 3.4 4.8
Max. cable cross-section, power [mm
2
]/[AWG]
2)
4/10 4/10 4/10 4/10
Max. pre-fuses [-]/UL
1)
[A]
16/6 16/6 16/10 16/10
Efficiency
3)
0.96 0.96 0.96 0.96
Weight IP 20 EB Bookstyle [kg] 7 7 7 7.5
Weight IP 20 EB Compact [kg] 8 8 8 8.5
Weight IP 54 Compact [kg] 11.5 11.5 11.5 12
Power loss at max. load [W] 55 67 92 110
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Series
16 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.