2.8.9. 6-6* Analog Output 2 (MCB 101)
Analog outputs are current outputs: 0/4 - 20 mA. Common terminal (terminal X30/7) is the same
terminal and electrical potential for analog common connection. Resolution on analog output is
12 bit.
6-60 Terminal X30/8 Output
Option: Function:
[0]
*
No operation
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor Current
[104] Torque re. to lim.
[105] Torque rel. to rated
[106] Power
[107] Speed
[108] Torque
[113] Ext. Closed Loop 1
[114] Ext. Closed Loop 2
[115] Ext. Closed Loop 3
[130] Output freq. 4-20 mA
[131] Reference 4-20 mA
[132] Feedback 4-20 mA
[133] Motor cur. 4-20 mA
[134] Torq. % lim 4-20 mA
[135] Torq. % nom 4-20 mA
[136] Power 4-20 mA
[137] Speed 4-20 mA
[138] Torque 4-20 mA
[139] Bus Ctrl 0-20 mA
[140] Bus Ctrl 4-20 mA
[141] Bus Ctrl timeout 0-20
mA
[142] Bus Ctrl timeout 4-20
mA
[143] Ext. Closed Loop 1
4-20 mA
[144] Ext. Closed Loop 2
4-20 mA
[145] Ext. Closed Loop 3
4-20 mA
6-61 Term. X30/8 Output Min Scale
Range: Function:
0%
*
[0.00 - 200 %] Scales the minimum output of the selected analog signal on ter-
minal X30/8. Scale the minimum value as a percentage of the