NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the
control keys [Hand on] – [Auto on].
[Reset
is used for resetting the frequency converter after an alarm (trip). The key can be
Enabled
[1] or
Disabled
[0] via par. 0-43
Reset Keys on LCP
.
The parameter shortcut
can be carried out by holding down the [Main Menu] key for 3 seconds. The parameter shortcut
allows direct access to any parameter.
1.1.2. Quick Transfer of Parameter Settings between Multiple Fre-
quency Converters
Once the set-up of a frequency converter is
complete, we recommend that you store the
data in the LCP or on a PC via MCT 10 Set-up
Software Tool.
Data storage in LCP:
1. Go to par. 0-50
LCP Copy
2. Press the [OK] key
3. Select “All to LCP”
4. Press the [OK] key
All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is
reached, press [OK].
You can now connect the LCP to another frequency converter and copy the parameter settings to
this frequency converter as well.
Data transfer from LCP to frequency converter:
1. Go to par. 0-50
LCP Copy
2. Press the [OK] key
3. Select “All from LCP”
4. Press the [OK] key
The parameter settings stored in the LCP are now transferred to the frequency converter indicated
by the progress bar. When 100% is reached, press [OK].
1.1.3. Display Mode
In normal operation, up to 5 different operating variables can be indicated continuously in the
middle section: 1.1, 1.2, and 1.3 as well as 2 and 3.
VLT
®
AQUA Drive Programming Guide 1. How to Programme
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
9
1

Other manuals for Danfoss vlt aqua