[33] Set digital output B
low
Any output with ‘digital output 2’ selected is low (off).
[34] Set digital output C
low
Any output with ‘digital output 3’ selected is low (off).
[35] Set digital output D
low
Any output with ‘digital output 4’ selected is low (off).
[36] Set digital output E
low
Any output with ‘digital output 5’ selected is low (off).
[37] Set digital output F
low
Any output with ‘digital output 6’ selected is low (off).
[38] Set digital output A
high
Any output with ‘digital output 1’ selected is high (closed).
[39] Set digital output B
high
Any output with ‘digital output 2’ selected is high (closed).
[40] Set digital output C
high
Any output with ‘digital output 3’ selected is high (closed).
[41] Set digital output D
high
Any output with ‘digital output 4’ selected is high (closed).
[42] Set digital output E
high
Any output with ‘digital output 5’ selected is high (closed).
[43] Set digital output F
high
Any output with ‘digital output 6’ selected is high (closed).
[60] Reset Counter A Resets Counter A to zero.
[61] Reset Counter B Resets Counter A to zero.
[70] Start Timer 3 Starts timer 3, see par. 13-20 for further description.
[71] Start Timer 4 Starts timer 4, see par. 13-20 for further description.
[72] Start Timer 5 Starts timer 5, see par. 13-20 for further description.
[73] Start Timer 6 Starts timer 6, see par. 13-20 for further description.
[74] Start Timer 7 Starts timer 7, see par. 13-20 for further description.
2.13. Main Menu - Special Functions -Group 14
2.13.1. 14-** Special Functions
Parameter group for configuring special frequency converter functions.
2.13.2. Inverter Switching, 14-0*
Parameters for configuring the inverter switching.
14-00 Switching Pattern
Option: Function:
[0]
*
60 AVM
[1] SFAVM Select the switching pattern: 60° AVM or SFAVM.
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
143
2