8-03 Control Timeout Time
Range: Function:
0 s
*
[0.1 - 18000 s] Enter the maximum time expected to pass between the recep-
tion of two consecutive telegrams. If this time is exceeded, it
indicates that the serial communication has stopped. The func-
tion selected in par. 8-04
Control Time-out Function
will then be
carried out.
In LonWorks the following variables will trigger the Control
Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-04 Control Timeout Function
Option: Function:
[0]
*
Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
[7] Select set-up 1
[8] Select set-up 2
[9] Select set-up 3
[10] Select set-up 4
[20] N2 Override Release
Select the time-out function. The time-out function activates
when the control word fails to be updated within the time period
specified in par. 8-03
Control Time-out Time
.
Choice [20] only appears after setting the N2 protocol.
In LonWorks the time-out function also activates, when the fol-
lowing SNVT's fail to be updated within the time period specified
in par. 8-03
Control Time-out Time
.
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
2. Parameter Description VLT
®
AQUA Drive Programming Guide
108
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
BrandDanfoss
Modelvlt aqua
CategoryDC Drives
LanguageEnglish

Related product manuals