EasyManuals Logo
Home>Danfoss>DC Drives>vlt aqua

Danfoss vlt aqua Programming Guide

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
This parameter defines which input will be used as the source
of the first feedback signal.
Analog input X30/11 and Analog input X30/12 refer to inputs on
the optional General Purpose I/O board.
NB!
If a feedback is not used, its source must be set to
No Function
[0]. Parameter 20-10
determines how the three possible feedbacks will be used by the PID Controller.
20-01 Feedback 1 Conversion
Option: Function:
[0]
*
Linear
[1] Square root This parameter allows a conversion function to be applied to
Feedback 1.
Linear
[0] has no effect on the feedback.
Square root
[1] is commonly used when a pressure sensor is
used to provide flow feedback (
(
flow
pressure
)
).
20-03 Feedback 2 Source
Option: Function:
See
Feedback 1 Source
, par. 20-00 for details.
20-04 Feedback 2 Conversion
Option: Function:
See
Feedback 1 Conversion
par. 20-01 for details.
20-06 Feedback 3 Source
Option: Function:
See
Feedback 1 Source
, par. 20-00 for details.
20-07 Feedback 3 Conversion
Option: Function:
See
Feedback 1 Conversion
, par. 20-01 for details.
20-12 Reference/Feedback Unit
Option: Function:
[0] None
[1]
*
%
[5] PPM
[10] 1/min
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
175
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
BrandDanfoss
Modelvlt aqua
CategoryDC Drives
LanguageEnglish

Related product manuals