EasyManuals Logo

Danfoss vlt aqua User Manual

Danfoss vlt aqua
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background image
3.10.3 Motor Thermal Protection
The electronic thermal relay in the adjustable frequency drive has received UL approval for single motor protection, when par. 1-90
Motor Thermal
Protection
is set for
ETR Trip
and par. 1-24
Motor Current
is set to the rated motor current (see motor nameplate).
For thermal motor protection, it is also possible to use the MCB 112 PTC thermistor card option. This card provides an ATEX certificate to protect motors
in explosion hazard areas, Zone 1/21 and Zone 2/22. Please refer to the
Design Guide
for further information.
3 How to Install VLT AQUA High Power Instruction Manual
3-76
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals