P250 P315 P355 P400
Normal Overload =110% current for 60 s HO NO HO NO HO NO HO NO
Typical shaft output at 400 V [kW] 250 315 315 355 355 400 400 450
Typical shaft output at 460 V [hp] 350 450 450 500 500 600 550 600
Typical shaft output at 480 V [kW] 315 355 355 400 400 500 500 530
Enclosure IP21/54 E9
Output current
Continuous (at 400 V) [A] 480 600 600 658 658 745 695 800
Intermittent (60 s overload) (at 400 V) [A] 720 660 900 724 987 820 1043 880
Continuous (at 460/480 V) [A] 443 540 540 590 590 678 678 730
Intermittent (60 s overload) (at 460/480 V)
[A]
665 594 810 649 885 746 1017 803
Continuous kVA (at 400 V) [kVA] 333 416 416 456 456 516 482 554
Continuous kVA (at 460 V) [kVA] 353 430 430 470 470 540 540 582
Continuous kVA (at 480 V) [kVA] 384 468 468 511 511 587 587 632
Max. Input current
Continuous (at 400 V) [A] 472 590 590 647 647 733 684 787
Continuous (at 460/480 V) [A] 436 531 531 580 580 667 667 718
Max. pre-fuses
1)
[A]
700 900
Max. cable size
Motor (mm
2
/AWG
2)
)
4x240 (4x500 mcm)
Line power (mm
2
/AWG
2
)
Load sharing (mm
2
/AWG
2)
)
Brake (mm
2
/AWG
2)
)
2x185 (2x350 mcm)
Total LHD loss 400 V AC [kW] 11587 14051 14140 15320 15286 17180 16036 18447
Total backchannel loss 400 V AC [kW] 9011 11301 10563 11648 11650 13396 12348 14570
Total lter loss 400 V AC [kW] 6528 7346 7346 7788 7788 8503 8060 8974
Total LHD loss 460 V AC [kW] 10962 12936 13124 14083 13998 15852 15847 16962
Total backchannel loss 460 V AC [kW] 8432 10277 9636 10522 10466 12184 12186 13214
Total lter loss 460 V AC [kW] 6316 7066 7006 7359 7326 8033 8033 8435
Weight, enclosure IP21, IP54 (lbs [kg]) 1314 [596] 1374 [623] 1425 [646]
Eciency
4)
0.96
Output frequency [Hz] 0–600
Heatsink overtemp. trip (°F [°C]) 221 [105]
Power card ambient trip (°F [°C]) 85
*High overload = 160% torque during 60 s; Normal overload = 110% torque during 60 s
Table 8.2 Line Power Supply 3x380–480 V AC
Specications Installation Manual
MG37A322 Danfoss A/S © Rev. 04/2015 All rights reserved. 87