2.1.5 Safe Stop of FC 300
The FC 302, and also the FC 301 in A1 enclosure, can perform the safety function
Safe Torque Off
(As defined by IEC 61800-5-2) or
Stop Category 0
(as
defined in EN 60204-1).
FC 301 A1 enclosure: When safe stop is included in the drive, position 18 of Type Code must be either T or U. If position 18 is B or X, Safe Stop Terminal
37 is not included!
Example:
Type Code for FC 301 A1 with Safe Stop: FC-301PK75T4Z20H4TGCXXXSXXXXA0BXCXXXXD0
It is designed and approved as suitable for the requirements of:
- Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1)
- Performance Level "d" in ISO EN 13849-1
- SIL 2 Capability in IEC 61508 and EN 61800-5-2
- SILCL 2 in EN 61062
This functionality is called Safe Stop. Prior to integration and use of safe stop in an installation, a thorough risk analysis must be carried out on the
installation in order to determine whether the safe stop functionality and safety levels are appropriate and sufficient.
After installing safe stop, a commissioning test as specified in section
Safe Stop Commissioning Test
of the Design Guide must be
performed. A passed commissioning test is mandatory for fulfilling Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1)
The following values are associated to the different types of safety levels:
Performance Level "d":
- MTTFD (Mean Time To Dangerous Failure): 24816 years
- DC (Diagnostic Coverage): 99.99%
- Category 3
SIL 2 Capability, SILCL 2:
- PFH (Probability of Dangerous failure per Hour) = 7e-10FIT = 7e-19/h
- SFF (Safe Failure Fraction) > 99%
- HFT (Hardware Fault Tolerance) = 0 (1oo1D architecture)
In order to install and use the safe stop function in accordance with the requirements of Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1), the related
information and instructions found in the VLT AutomationDrive Design Guide MG.33.BX.YY must be followed! The information and instructions of the
Instruction Manual are not sufficient for a correct and safe use of the safe stop functionality!
2 Safety Instructions and General Warning
VLT
®
AutomationDrive FC 300 Instruction
Manual
2-4
MG.33.AG.22 - VLT
®
is a registered Danfoss trademark
2

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals