ALARM 247, Power card temperature
This alarm is only for F Frame drives. It is equivalent to Alarm 69. The
report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in F2 or F4 drive.
2 = right inverter module in F1 or F3 drive.
3 = right inverter module in F2 or F4 drive.
5 = rectifier module.
ALARM 248, Illegal power section configuration
This alarm is only for F Frame drives. It is equivalent to Alarm 79. The
report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in F2 or F4 drive.
2 = right inverter module in F1 or F3 drive.
3 = right inverter module in F2 or F4 drive.
5 = rectifier module.
ALARM 250, New Spare Part:
The power or Switch Mode Power Supply has been exchanged. The ad-
justable frequency drive type code must be restored in the EEPROM. Se-
lect the correct type code in par. 14-23
Typecode Setting
according to
the label on unit. Remember to select ‘Save to EEPROM’ to complete.
ALARM 251, New Type Code:
The adjustable frequency drive has a new type code.
6 Troubleshooting
VLT
®
AutomationDrive FC 300 Instruction
Manual
6-10
MG.33.AG.22 - VLT
®
is a registered Danfoss trademark
6