10 Specifications
10.1 Power-dependent Specifications
Line Power Supply 3 x 200–240V AC
FC 301/FC 302 PK25 PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0 P3K7
Typical Shaft Output [kW] 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 3.7
Enclosure IP20/IP21 A2 A2 A2 A2 A2 A2 A2 A3 A3
Enclosure IP 20 (FC 301 only) A1 A1 A1 A1 A1 A1 - - -
Enclosure IP 55, 66 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5
Output current
Continuous
(3 x 200–240V) [A]
1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7
Intermittent
(3 x 200–240V) [A]
2.9 3.8 5.6 7.4 10.6 12.0 17.0 20.0 26.7
Continuous
kVA (208V AC) [kVA]
0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00
Max. input current
Continuous
(3 x 200–240V) [A]
1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0
Intermittent
(3 x 200–240V) [A]
2.6 3.5 5.1 6.6 9.4 10.9 15.2 18.1 24.0
Additional specifications
Max. cable size (line power, motor,
brake) [mm
2
(AWG
2)
)]
0.2–4 (24–10)
Estimated power loss
at rated max. load [W]
4)
21 29 42 54 63 82 116 155 185
Weight, enclosure IP20 [kg] 4.7 4.7 4.8 4.8 4.9 4.9 4.9 6.6 6.6
A1 (IP20) 2.7 2.7 2.7 2.7 2.7 2.7 - - -
A5 (IP 55, 66) 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
Efficiency
4)
0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.96
0.25–3.7 kW only available as 160% high overload.
Line Power Supply 3 x 200–240V AC
FC 301/FC 302 P5K5 P7K5 P11K
High/ Normal Load
1)
HO NO HO NO HO NO
Typical Shaft Output [kW] 5.5 7.5 7.5 11 11 15
Enclosure IP20 B3 B3 B4
Enclosure IP21 B1 B1 B2
Enclosure IP55, 66 B1 B1 B2
Output current
Continuous
(3 x 200–240V) [A]
24.2 30.8 30.8 46.2 46.2 59.4
Intermittent
(60 sec overload)
(3 x 200–240V) [A]
38.7 33.9 49.3 50.8 73.9 65.3
Continuous
kVA (208V AC) [kVA]
8.7 11.1 11.1 16.6 16.6 21.4
Max. input current
Continuous
(3 x 200–240V) [A]
22 28 28 42 42 54
Intermittent
(60 sec overload)
(3 x 200–240V) [A]
35.2 30.8 44.8 46.2 67.2 59.4
Additional specifications
Max. cable size [mm
2
(AWG)]
2)
16 (6) 16 (6) 35 (2)
Max cable size with line power disconnect 16 (6)
Estimated power loss
at rated max. load [W]
4)
239 310 371 514 463 602
Weight,
enclosure IP21, IP55, 66 [kg]
23 23 27
Efficiency
4)
0.964 0.959 0.964
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark 10-1
10
10

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 303 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 303
CategoryDC Drives
LanguageEnglish

Related product manuals