Line Power Supply 3 x 380–500V AC (FC 302), 3 x 380–480V AC (FC 301)
PK 37 PK 55 PK75 P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
FC 301/FC 302
Typical Shaft Output [kW]
0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5
Enclosure IP20/IP21 A2 A2 A2 A2 A2 A2 A2 A2 A3 A3
Enclosure IP20 (FC 301 only) A1 A1 A1 A1 A1
Enclosure IP 55, 66 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5
Output current
High overload 160% for 1 min.
Shaft output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5
Continuous
(3 x 380–440V) [A]
1.3 1.8 2.4 3 4.1 5.6 7.2 10 13 16
Intermittent
(3 x 380–440V) [A]
2.1 2.9 3.8 4.8 6.6 9.0 11.5 16 20.8 25.6
Continuous
(3 x 441–500V) [A]
1.2 1.6 2.1 2.7 3.4 4.8 6.3 8.2 11 14.5
Intermittent
(3 x 441–500V) [A]
1.9 2.6 3.4 4.3 5.4 7.7 10.1 13.1 17.6 23.2
Continuous kVA
(400V AC) [kVA]
0.9 1.3 1.7 2.1 2.8 3.9 5.0 6.9 9.0 11.0
Continuous kVA
(460V AC) [kVA]
0.9 1.3 1.7 2.4 2.7 3.8 5.0 6.5 8.8 11.6
Max. input current
Continuous
(3 x 380–440V) [A]
1.2 1.6 2.2 2.7 3.7 5.0 6.5 9.0 11.7 14.4
Intermittent
(3 x 380–440V) [A]
1.9 2.6 3.5 4.3 5.9 8.0 10.4 14.4 18.7 23.0
Continuous
(3 x 441–500V) [A]
1.0 1.4 1.9 2.7 3.1 4.3 5.7 7.4 9.9 13.0
Intermittent
(3 x 441–500V) [A]
1.6 2.2 3.0 4.3 5.0 6.9 9.1 11.8 15.8 20.8
Additional specifications
Max. cable size
(line power, motor, brake)
[AWG]
2)
[mm
2
]
24–10 AWG
0.2–4 mm
2
24–10 AWG
0.2–4 mm
2
Estimated power loss
at rated max. load [W]
4)
35 42 46 58 62 88 116 124 187 255
Weight,
enclosure IP20
4.7 4.7 4.8 4.8 4.9 4.9 4.9 4.9 6.6 6.6
Enclosure IP 55, 66 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 14.2 14.2
Efficiency
4)
0.93 0.95 0.96 0.96 0.97 0.97 0.97 0.97 0.97 0.97
0.33–10 hp [0.37–7.5 kW] only available as 160% high overload.
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark 10-3