Design Guide | VLT® AutomationDrive FC 360
Table 4: Electrical Data for High Overload, Mains Supply 3x380–480 V AC (continued)
Drive H90K H110 H132 H160 H200 H250
Output current (3-phase)
Continuous (at 400 V) [A] 177 212 260 315 395 480
Intermittent (60 s overload) (at 400 V) [A] 266 318 390 473 593 720
Continuous (at 460 V) [A] 160 190 240 302 361 443
Intermittent (60 s overload) (at 460 V) [A] 240 285 360 453 542 665
Continuous kVA (at 400 V) [kVA] 123 147 180 218 274 333
Continuous kVA (at 460 V) [kVA] 127 151 191 241 288 353
Maximum input current
Continuous (at 400 V) [A] 171 204 251 304 381 463
Continuous (at 460 V) [A] 154 183 231 291 348 427
Maximum number and size of cables per phase
Mains and motor [mm
2
(AWG)] 2x95 (2x3/0) 2x185 (2x350 mcm)
Maximum external mains fuses [A] 315 350 400 550 630 800
Estimated power loss at 400 V [W] 2031 2289 2923 3093 4039 5004
Estimated power loss at 460 V [W] 1828 2051 2089 2872 3575 4458
Efficiency [%] 98
Output frequency [Hz] 0–590
Heat sink overtemperature trip [°C (°F)] 110 (230)
Control card overtemperature trip [°C (°F)] 75 (167) 80 (176)
5.2 Mains Supply (L1, L2, L3)
Supply voltage 380–480 V ±10%
Supply frequency 50/60 Hz ±5%
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
(1)
True power factor (λ) ≥0.9 nominal at rated load
Displacement power factor (cos Φ) near unity >0.98
Switching on input supply L1, L2, L3 (power-ups) Maximum 1 time/2 minute
Environment according to EN60664-1 Overvoltage category III/pollution degree 2
1) Calculations based on IEC61800-3.
Mains voltage low/mains voltage drop-out: