THDv= 0%
THDv= 5%
Leakage current
Figure 29: Line Distortion Influences Leakage Current
If the leakage current exceeds 3.5 mA, compliance with EN/IEC61800-5-1 (power drive system product standard) requires special care.
Reinforce grounding with the following protective earth connection requirements:
l Ground wire (terminal 95) of at least 10 mm
2
(8 AWG) cross-section.
l 2 separate ground wires both complying with the dimensioning rules.
See EN/IEC61800-5-1 and EN 50178 for further information.
Using RCDs
Where residual current devices (RCDs), also known as Ground Leakage Circuit Breakers, are used, comply with the following:
l Use RCDs of type B only as they can detect AC and DC currents.
l Use RCDs with a delay to prevent faults due to transient ground currents.
l Dimension RCDs according to the system configuration and environmental considerations.
The leakage current includes several frequencies originating from both the mains frequency and the switching frequency. Whether the
switching frequency is detected depends on the type of RCD used.
62 | Danfoss A/S © 2024.01 AJ435824192086en-000101 / 130R1295
Design Guide | VLAutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals