FC 302
N315
N355
N400
Intermittent (60 s overload) (at 460/500 V) [A]
810
649
885
746
1017
803
Continuous kVA (at 400 V) [kVA]
416
456
456
516
482
554
Continuous kVA (at 460 V) [kVA]
430
470
470
540
540
582
Continuous kVA (at 500 V) [kVA]
468
511
511
587
587
632
Maximum input current
Continuous (at 400 V) [A]
578
634
634
718
670
771
Continuous (at 460/500 V) [A]
520
569
569
653
653
704
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
- Mains with disconnect [mm
2
(AWG)]
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
- Mains with contactor [mm
2
(AWG)]
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
- Motor [mm
2
(AWG)]
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
Drive module power loss at 400 V [W]
(1)(2)(3)
6178
6928
6851
8036
7297
8783
Drive module power loss at 460 V [W]
(1)(2)(3)
5322
5910
5846
6933
7240
7969
Drive efficiency
(2)
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
145 (293)
145 (293)
145 (293)
Line reactor overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Sine-wave filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the Ambient Conditions section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also Input Power Option Losses section.
4
If using an output filter, the output frequency is limited further. See
10.3.1 Motor Output (U, V, W).
Table 104: Electrical Data, Mains Supply 3x380–500 V AC
FC 302
N450
N500
High/normal overload
HO
NO
HO
NO
AQ262139143212en-000301 / 130R0879164 | Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals