EasyManuals Logo
Home>Danfoss>DC Drives>VLT CANopen MCA 105

Danfoss VLT CANopen MCA 105 User Manual

Danfoss VLT CANopen MCA 105
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
XD2 ter-
minal
Parameter
Default setting
Description
17
Parameter 5-15 Terminal 33 Digital
Input
[0] No operation
14
Parameter 5-12 Terminal 27 Digital
Input
[2] Coast inverse
For digital input or output. Default setting is input.
15
Parameter 5-13 Terminal 29 Digital
Input
[14] JOG
18
Common for digital inputs and 0 V potential for 24 V supply.
19
STO
When not using the optional STO feature, a jumper wire is re-
quired between terminal XD2.10 (or XD2.11) and terminal
XD2.19. This set-up allows the drive to operate with factory
default programming values.
Table 45: Analog Input/Output Terminal Descriptions
XD2 ter-
minal
Parameter
Default setting
Description
4
Common for analog output.
5
Parameter 6-50 Terminal 42 Out-
put
[0] No operation
Programmable analog output. 0–20 mA or 4–20 mA at a maxi-
mum of 500 Ω.
6
+10 V DC
10 V DC analog supply voltage for potentiometer or thermis-
tor. 15 mA maximum.
7
Parameter group 6-1* Analog In-
put 1
Reference
Analog input. For voltage (V) or current (mA).
8
Parameter group 6-2* Analog In-
put 2
Feedback
9
Common for analog input.
5.7.4 Relay Terminals
Table 46: Relay Terminal Descriptions
XD2 terminal
Parameter
Default setting
Description
21, 22, 23
Parameter 5-40 Function Relay [0]
[0] No operation
Form C relay outputs. For AC or DC voltage.
24, 25, 26
Parameter 5-40 Function Relay [1]
[0] No operation
5.7.5 Option Card Terminals
The option cards extend the functionality of drives and provide a high variety of interfaces to automation systems. When the option
cards are specified in the type code, they are mounted in slots A, B, C, and D of the control card within the drive module. The option
card wiring is routed to a terminal block within the control compartment. For more details, refer to the Installation/Operating Guide
for the respective option card.
N O T I C E
OPTION CARD INSTALLATION
If the option card is ordered along with the drive using the type code, the factory installs the option card and its wiring. If the
option is ordered separately, the customer is responsible for installing the option card and the wiring extensions to the control
compartment.
AQ262139143212en-000301 / 130R087984 | Danfoss A/S © 2021.10
Electrical Installation
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals