2.5.4 Example of Process PID Control
Illustration 2.14 is an example of a Process PID Control
used in a ventilation system:
Temperature
Fan speed
Temperature
transmitter
Heat
Heat
generating
process
Cold air
130BA218.10
100kW
n °CW
Illustration 2.14 Process PID Control in a Ventilation System
In a ventilation system, the temperature is to be settable
from - 5 to 35 °C with a potentiometer of 0-10 V. The set
temperature must be kept constant, for which purpose the
Process Control is to be used.
The control is of the inverse type, which means that when
the temperature increases, the ventilation speed is
increased as well, so as to generate more air. When the
temperature drops, the speed is reduced. The transmitter
used is a temperature sensor with a working range of -10
to 40 °C, 4-20 mA. Min./Max. speed 300/1500 RPM.
Transmitter
96 97 9998
91 92 93 95
50
12
L1 L2
L1
PEL3
W PEVU
F1
L2
L3
N
PE
130BD373.10
18
53
27
55
54
M
3
Illustration 2.15 Two-wire Transmitter
1. Start/Stop via switch connected to terminal 18.
2. Temperature reference via potentiometer (-5 to
35 °C, 0-10 V DC) connected to terminal 53.
3. Temperature feedback via transmitter (-10 to 40
°C, 4-20 mA) connected to terminal 54.
Product Overview
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark 29
2 2