3.10.2 Force/Write Single Coil (05 HEX)
Description
This function forces the coil to either ON or OFF. When
broadcast the function forces the same coil references in
all attached slaves.
Query
The query message specifies the coil 65 (parameter write
control) to be forced. Coil addresses start at zero, that is,
coil 65 is addressed as 64. Force Data=00 00HEX (OFF) or
FF 00HEX (ON).
Field Name Example (HEX)
Slave Address 01 (Frequency converter address)
Function 05 (write single coil)
Coil Address HI 00
Coil Address LO 40 (64 decimal) Coil 65
Force Data HI FF
Force Data LO 00 (FF 00=ON)
Error Check (CRC) -
Table 3.23 Query
Response
The normal response is an echo of the query, returned
after the coil state has been forced.
Field Name
Example (HEX)
Slave Address 01
Function 05
Force Data HI FF
Force Data LO 00
Quantity of Coils HI 00
Quantity of Coils LO 01
Error Check (CRC) -
Table 3.24 Response
3.10.3
Force/Write Multiple Coils (0F HEX)
This function forces each coil in a sequence of coils to
either ON or OFF. When broadcast the function forces the
same coil references in all attached slaves.
The query message specifies the coils 17 to 32 (speed set-
point) to be forced.
Field Name
Example (HEX)
Slave Address 01 (frequency converter address)
Function 0F (write multiple coils)
Coil Address HI 00
Coil Address LO 10 (coil address 17)
Quantity of Coils HI 00
Quantity of Coils LO 10 (16 coils)
Byte Count 02
Force Data HI
(Coils 8-1)
20
Force Data LO
(Coils 16-9)
00 (ref.=2000 hex)
Error Check (CRC) -
Table 3.25 Query
Response
The normal response returns the slave address, function
code, starting address, and quantity of coils forced.
Field Name Example (HEX)
Slave Address 01 (frequency converter address)
Function 0F (write multiple coils)
Coil Address HI 00
Coil Address LO 10 (coil address 17)
Quantity of Coils HI 00
Quantity of Coils LO 10 (16 coils)
Error Check (CRC) -
Table 3.26 Response
3.10.4
Read Holding Registers (03 HEX)
Description
This function reads the contents of holding registers in the
slave.
Query
The query message specifies the starting register and
quantity of registers to be read. Register addresses start at
zero, that is, registers 1-4 are addressed as 0-3.
Example: Read 3-03 Maximum Reference, register 03030.
Field Name
Example (HEX)
Slave Address 01
Function 03 (read holding registers)
Starting Address HI 0B (Register address 3029)
Starting Address LO 05 (Register address 3029)
No. of Points HI 00
No. of Points LO
02 - (3-03 Maximum Reference is 32 bits
long, i.e. 2 registers)
Error Check (CRC) -
Table 3.27 Query
RS-485 Installation and Set...
VLT
®
AutomationDrive FC 360 Design Guide
54 MG06B202 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 360 and is the answer not in the manual?

Danfoss VLT FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals