2.6.2 EMC Test Results
The test results in Table 2.11 have been obtained using a system with a frequency converter (with options if relevant), a
screened control cable, a control box with potentiometer, as well as a motor and motor screened cable.
RFI filter type Conducted emission Radiated emission
Standards and requirements
EN 55011
Class A Group 2
Industrial
environment
Class A Group 1
Industrial environment
EN/IEC 61800-3
Category C3
Second environment
Industrial
Category C2
First environment Home and
office
J1 0.37-2.2 kW, 380-480 V 25 m Yes
J2 3.0-5.5 kW, 380-480 V 25 m Yes
J3 7.5 kW, 380-480 V 25 m Yes
J4 11-15 kW (380-480 V) 25 m Yes
J5 18.5-22 kW (380-480 V) 25 m Yes
Table 2.11 EMC Test Results (Emission, Immunity)