Danfoss Drives · DKDD.PB.551.A1.02 | 11
These duty ratings dene the load requirements, not
the starter capabilities. Starter capability is specied
separately in User Manuals, Product Guides and
WinStart. Use these charts to select a soft starter for a
particular application.
Current Ratings
Normal Heavy Severe
MCD5-0021B 21 (32) 17 (26) 15 (22)
MCD5-0037B 37 (56) 31 (47) 26 (39)
MCD5-0043B 43 (65) 37 (56) 30 (45)
MCD5-0053B 53 (80) 46 (69) 37 (55)
MCD5-0068B 68 (102) 55 (83) 47 (71)
MCD5-0084B 84 (126) 69 (104) 58 (87)
MCD5-0089B 89 (134) 74 (112) 61 (92)
MCD5-0105B 105 (158) 95 (143) 78 (117)
MCD5-0131B 131 (197) 106 (159) 90 (136)
MCD5-0141B 141 (212) 121 (181) 97 (146)
MCD5-0195B 195 (293) 160 (241) 134 (201)
MCD5-0215B 215 (323) 178 (268) 149 (223)
MCD5-0245C 255 (383) 201 (302) 176 (264)
MCD5-0245B 245 (368) 194 (291) 169 (254)
MCD5-0331B 331 (497) 266 (400) 229 (343)
MCD5-0360C 360 (540) 310 (465) 263 (395)
MCD5-0380C 380 (570) 359 (539) 299 (449)
MCD5-0396B 396 (594) 318 (478) 273 (410)
MCD5-0428C 430 (645) 368 (552) 309 (463)
MCD5-0469B 469 (704) 383 (575) 326 (490)
MCD5-0525B 525 (787) 425 (637) 364 (546)
MCD5-0595C 620 (930) 540 (810) 434 (651)
MCD5-0619C 650 (975) 561 (842) 455 (683)
MCD5-0632B 632 (948) 512 (768) 438 (658)
MCD5-0790C 790 (1185) 714 (1072) 579 (869)
MCD5-0744B 74 4 (1116) 606 (910) 516 (774)
MCD5-0826B 826 (1239) 684 (1026) 571 (857)
MCD5-0927C 930 (1395) 829 (1244) 661 (992)
MCD5-0961B 961 (1441) 796 (119 4) 664 (997)