Danfoss Drives · DKDD.PB.551.A1.02 | 35
Semiconductor fuses may be used with MCD soft starters. Use
of semiconductor fuses will provide Type 2 coordination and
reduce the potential of SCR damage due to transient overload
currents and short circuits. MCD soft starters have been tested
to achieve Type 2 coordination with semiconductor fuses. The
following table provides a list of suitable Bussman fuses. If
selecting alternate brands ensure the selected fuse has a lower
total clearing I2t rating than the SCR, and can carry start current
for the full start duration.
MCD 200
200~575 V
SCR I
2
t
(A
2
s)
Bussmann Fuse
Square Body (170M)
Bussmann Fuse
British Style (BS88)
MCD200-007 170M -1314 63 FE 1150
MCD200-015 170M-1317 160 FEE 8000
MCD200-018 170M-1318 160 FEE 10500
MCD200-022 170M-1318 180 FM 15000
MCD200-030 170M-1319 180 FM 18000
MCD200-037 170M-1321 250 FM 51200
MCD200-045 170M-1321 250 FM 80000
MCD200-055 170M-1321 250 FM 97000
MCD200-075 170M-1322 500 FMM 168000
MCD200-090 170M-3022 500 FMM 245000
MCD20 0 -110 170M-3022 500 FMM 320000
Semiconductor Fuse Selection: Type 2

Other manuals for Danfoss VLT MCD 201

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 201 and is the answer not in the manual?

Danfoss VLT MCD 201 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 201
CategoryController
LanguageEnglish

Related product manuals