• Semiconductor fuses may be used with MCD soft starters. Use
of semiconductor fuses will provide Type 2 coordination and
reduce the potential of SCR damage due to transient overload
currents and short circuits. MCD soft starters have been tested
to achieve Type 2 coordination with semiconductor fuses. The
following table provides a list of suitable Bussman fuses. If
selecting alternate brands ensure the selected fuse has a lower
total clearing I2t rating than the SCR, and can carry start current
for the full start duration.
MCD 200
200~575 V
SCR I
2
t
(A
2
s)
Bussmann Fuse
Square Body (170M)
Bussmann Fuse
British Style (BS88)
MCD200-007 170M -1314 63 FE 1150
MCD200-015 170M-1317 160 FEE 8000
MCD200-018 170M-1318 160 FEE 10500
MCD200-022 170M-1318 180 FM 15000
MCD200-030 170M-1319 180 FM 18000
MCD200-037 170M-1321 250 FM 51200
MCD200-045 170M-1321 250 FM 80000
MCD200-055 170M-1321 250 FM 97000
MCD200-075 170M-1322 500 FMM 168000
MCD200-090 170M-3022 500 FMM 245000
MCD20 0 -110 170M-3022 500 FMM 320000
Semiconductor Fuse Selection: Type 2