24 | Danfoss Drives · DKDD.PB.551.A1.02
NEMA 250 is a product standard for enclosure design and
performance.
NEMA Protection against solid objects Approx. IP equivalent
1 Indoor, protection from contact. IP 23
2
Indoor, limited protection from
dirt and water.
IP 30
3
Outdoor, some protection from rain,
sleet, windblown dust and ice.
IP 64
3R
Outdoor, some protection from rain,
sleet and ice.
IP 32
4
Indoor or outdoor, some protection from
windblown dust, rain, splashing water,
hose-directed water and ice.
IP 66
4X
Indoor or outdoor, some protection
from corrosion, windblown dust, rain,
splashing water, hose-directed water
and ice.
IP 66
6
Indoor or outdoor, some protection from
ice, hose-directed water, entry of water
when submerged at limited depth.
IP 67
12
Indoor, protection from dust, falling dirt
and dripping non-corrosive liquids.
IP 55
13
Indoor, protection from dust, spraying
water, oil and non-corrosive liquids.
IP 65
Warning:
Conversion from NEMA to IEC (IP) degrees of enclosure not to be
used for converting from IEC to NEMA.
Please refer to NEMA publication 250, 2003.
NEMA ratings

Other manuals for Danfoss VLT MCD 201

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 201 and is the answer not in the manual?

Danfoss VLT MCD 201 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 201
CategoryController
LanguageEnglish

Related product manuals