3-1* References
3-10 Preset Reference
-100.0-100.0% *0.00%
3-11 Jog Speed [Hz]
0.0-400.0 Hz *5.0 Hz
3-12 Catch up/slow Down Value
0.00-100.0% *0.00%
3-14 Preset Relative Reference
-100.0-100.0% *0.00%
3-15 Reference Resource 1
[0] No function
*[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] LCP Potentiometer
3-16 Reference Resource 2
[0] No function
[1] Analog Input 53
*[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] LCP Potentiometer
3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] LCP Potentiometer
3-18 Relative Scaling Ref.
Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] LCP Potentiometer
3-4* Ramp 1
3-40 Ramp 1 Type
*[0] Linear
[2] Sine2 ramp
3-41 Ramp 1 Ramp up Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-42 Ramp 1 Ramp Down Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-5* Ramp 2
3-50 Ramp 2 Type
*[0] Linear
[2] Sine2 ramp
3-51 Ramp 2 Ramp up Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-52 Ramp 2 Ramp down Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-8* Other Ramps
3-80 Jog Ramp Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-81 Quick Stop Ramp Time
0.05-3600 s *3.00 s(10.00 s
1)
)
4-** Limits/Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
[0] Clockwise if Par. 1-00 is set to
[3]
[1] CounterClockwise
*[2] Both if Par. 1-00 is set to [0]
4-12 Motor Speed Low Limit [Hz]
0.0-400.0 Hz * 0.0 Hz
4-14 Motor Speed High Limit [Hz]
0.1-400.0 Hz *65.0 Hz
4-16 Torque Limit Motor Mode
0-400% *150%
4-17 Torque Limit Generator
Mode
0-400% *100%
4-4* Adj. Warnings 2
4-40 Warning Frequency Low
0.00-Value of 4-41 Hz *0.0 Hz
4-41 Warning Frequency High
Value of 4-40-400.0 Hz *400.0 Hz
4-5* Adj. Warnings
4-50 Warning Current Low
0.00-100.00 A *0.00 A
4-51 Warning Current High
0.00-100.00 A *100.00 A
4-54 Warning Reference Low
-4999.000-Value of 4-55
*-4999.000
4-55 Warning Reference High
Value of 4-54-4999.000 *4999.000
4-56 Warning Feedback Low
-4999.000-Value of 4-57
*-4999.000
4-57 Warning Feedback High
Value of 4-56-4999.000 *4999.000
4-58 Missing Motor Phase
Function
[0] Off
*[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0.0-400.0 Hz * 0.0 Hz
4-63 Bypass Speed To [Hz]
0.0-400.0 Hz * 0.0 Hz
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No function
[1] Reset
[2] Coast inverse
[3] Coast and reset inv.
[4] Quick stop inverse
[5] DC-brake inv.
[6] Stop inv
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[16-18] Preset ref bit 0-2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Setup select bit 0
[28] Catch up
[29] Slow down
[34] Ramp bit 0
[60] Counter A (up)
[61] Counter A (down)
[62] Reset counter A
[63] Counter B (up)
[64] Counter B (down)
[65] ResetCounter B
5-11 Terminal 19 Digital Input
See par. 5-10. *[10] Reversing
5-12 Terminal 27 Digital Input
See par. 5-10. * [1] Reset
5-13 Terminal 29 Digital Input
See par. 5-10. * [14] Jog
5-15 Terminal 33 Digital Input
See par. 5-10. * [16] Preset ref bit
0
[26] Precise Stop Inverse
[27] Start, Precise Stop
[32] Pulse Input
5-3* Digital Outputs
5-34 On Delay, Terminal 42
Digital Output
0.00-600.00 s *0.01 s
5-35 Off Delay, Terminal 42
Digital Output
0.00-600.00 s *0.01 s
5-4* Relays
5-40 Function Relay
*[0] No operation
[1] Control ready
[2] Drive ready
[3] Drive ready, Remote
[4] Enable/No warning
[5] Drive running
[6] Running/No warning
[7] Run in range/No warning
[8] Run on ref/No warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[16] Below frequency, low
[17] Above frequency, high
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[22] Ready, No thermal warning
[23] Remote ready, No thermal
warning
[24] Ready, Voltage ok
[25] Reverse
[26] Bus ok
[28] Brake,NoWarn
[29] Brake ready/NoFault
[30] BrakeFault (IGBT)
[32] Mech.brake control
[36] Control word bit 11
[41] Below reference, low
[42] Above reference, high
[51] Local ref. active
[52] Remote ref. active
[53] No alarm
[54] Start cmd active
[55] Running reverse
[56] Drive in hand mode
[57] Drive in auto mode
[60-63] Comparator 0-3
[70-73] Logic rule 0-3
[81] SL digital output B
5-41 On Delay, Relay
0.00-600.00 s *0.01 s
5-42 Off Delay, Relay
0.00-600.00 s *0.01 s
5-5* Pulse Input
5-55 Terminal 33 Low Frequency
20-4999 Hz * 20 Hz
5-56 Terminal 33 High Frequency
21-5000 Hz *5000 Hz
5-57 Term. 33 Low Ref./Feedb.
Value
-4999-4999 *0.000
5-58 Term. 33 High Ref./Feedb.
Value
-4999-4999 *50.000
6-** Analog In/Out
1)
M4 and M5 only
Table 5.2
Parameter Lists
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark 51
5 5

Other manuals for Danfoss VLT Micro Drive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive and is the answer not in the manual?

Danfoss VLT Micro Drive Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive
CategoryDC Drives
LanguageEnglish

Related product manuals