6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
1-99 s *10 s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
0.00-9.99 V *0.07 V
6-11 Terminal 53 High Voltage
0.01-10.00 V *10.00 V
6-12 Terminal 53 Low Current
0.00-19.99 mA *0.14 mA
6-13 Terminal 53 High Current
0.01-20.00 mA *20.00 mA
6-14 Term. 53 Low Ref./Feedb.
Value
-4999-4999 *0.000
6-15 Term. 53 High Ref./Feedb.
Value
-4999-4999 *50.000
6-16 Terminal 53 Filter Time
Constant
0.01-10.00 s *0.01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2* Analog Input 2
6-22 Terminal 60 Low Current
0.00-19.99 mA *0.14 mA
6-23 Terminal 60 High Current
0.01-20.00 mA *20.00 mA
6-24 Term. 60 Low Ref./Feedb.
Value
-4999-4999 *0.000
6-25 Term. 60 High Ref./Feedb.
Value
-4999-4999 *50.00
6-26 Terminal 60 Filter Time
Constant
0.01-10.00 s *0.01 s
6-8* LCP potentiometer
6-80 LCP LCP Potmeter Enable
[0] Disabled
[1] * Enable
6-81 LCP potm. Low Reference
-4999-4999 *0.000
6-82 LCP potm. High Reference
-4999-4999 *50.00
6-9* Analog Output xx
6-90 Terminal 42 Mode
*[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Bus Reference
6-92 Terminal 42 Digital Output
See par. 5-40
*[0] No Operation
[80] SL Digital Output A
6-93 Terminal 42 Output Min
Scale
0.00-200.0%
*0.00%
6-94 Terminal 42 Output Max
Scale
0.00-200.0% *100.0%
7-** Controllers
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1
Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
7-3* Process PI
Ctrl. 7-30 Process PI Normal/
Inverse Ctrl
*[0] Normal
[1] Inverse
7-31 Process PI Anti Windup
[0] Disable
*[1] Enable
7-32 Process PI Start Speed
0.0-200.0 Hz *0.0 Hz
7-33 Process PI Proportional Gain
0.00-10.00 *0.01
7-34 Process PI Integral Time
0.10-9999 s *9999 s
7-38 Process PI Feed Forward
Factor
0-400% *0%
7-39 On Reference Bandwidth
0-200% *5%
8-** Comm. and Options
8-0* General Settings
8-01 Control Site
*[0] Digital and ControlWord
[1] Digital only
[2] ControlWord only
8-02 Control Word Source
[0] None
*[1] FC RS485
8-03 Control Word Timeout Time
0.1-6500 s *1.0 s
8-04 Control Word Timeout
Function
*[0] Off
[1] Freeze Output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
8-06 Reset Control Word Timeout
*[0] No Function
[1] Do reset
8-3* FC Port Settings
8-30 Protocol
*[0] FC
[2] Modbus
8-31 Address
1-247 *1
8-32 FC Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud For choosing FC
bus in 8-30
* [3] 19200 Baud For choosing
FC bus in 8-30
*[4] 38400 Baud
8-33 FC Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001-0.5 *0.010 s
8-36 Max Response Delay
0.100-10.00 s *5.000 s
8-4* FC MC protocol set
8-43 FC Port PCD Read Configu-
ration
*[0] None Expressionlimit
[1] [1500] Operation Hours
[2] [1501] Running Hours
[3] [1502] kWh Counter
[4] [1600] Control Word
[5] [1601] Reference [Unit]
[6] [1602] Reference %
[7] [1603] Status Word
[8] [1605] Main Actual Value [%]
[9] [1609] Custom Readout
[10] [1610] Power [kW]
[11] [1611] Power [hp]
[12] [1612] Motor Voltage
[13] [1613] Frequency
[14] [1614] Motor Current
[15] [1615] Frequency [%]
[16] [1618] Motor Thermal
[17] [1630] DC Link Voltage
[18] [1634] Heatsink Temp.
[19] [1635] Inverter Thermal
[20] [1638] SL Controller State
[21] [1650] External Reference
[22] [1651] Pulse Reference
[23] [1652] Feedback [Unit]
[24] [1660] Digital Input
18,19,27,33
[25] [1661] Digtial Input 29
[26] [1662] Analog Input 53(V)
[27] [1663] Analog Input 53(mA)
[28] [1664] Analog Input 60
[29] [1665] Analog Output 42
[mA]
[30] [1668] Freq. Input 33 [Hz]
[31] [1671] Relay Output [bin]
[32] [1672] Counter A
[33] [1673] Counter[34] [1690]
Alarm Word
[34] [1690] Alarm Word
[35] [1692] Warning Word
[36] [1694] Ext. Status Word
8-5* Digital/Bus
8-50 Coasting Select
[0] DigitalInput
[1] Bus
[2] LogicAnd
*[3] LogicOr
8-51 Quick Stop Select
See par. 8-50 * [3] LogicOr
8-52 DC Brake Select
See par. 8-50 * [3] LogicOr
8-53 Start Select
See par. 8-50 * [3] LogicOr
8-54 Reversing Select
See par. 8-50 * [3] LogicOr
8-55 Set-up Select
See par. 8-50 * [3] LogicOr
8-56 Preset Reference Select
See par. 8-50 * [3] LogicOr
8-8X Bus communication
Diagnostics
8-80 Bus Message Count
0-0 N/A *0 N/A
8-81 Bus Error Count
0-0 N/A *0 N/A
8-82 Slave Messages Rcvd
0-0 N/A *0 N/A
8-83 Slave Error Count
0-0 N/A *0 N/A
Table 5.3
Parameter Lists
VLT
®
Micro Drive FC 51 Programming Guide
52 MG02C602 - VLT
®
is a registered Danfoss trademark
55

Other manuals for Danfoss VLT Micro Drive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive and is the answer not in the manual?

Danfoss VLT Micro Drive Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive
CategoryDC Drives
LanguageEnglish

Related product manuals