3.5.2
Mounting in a VLT
®
DriveMotor FCP
106 Frequency Converter
1. Remove the lid from the frequency converter.
2. Check whether the
eldbus option is already
mounted in the frequency converter. If already
mounted, go to step 4. If not mounted, go to
step 3.
3. Mount the eldbus option.
4. Set the termination switch (shown in
Illustration 3.7) on the eldbus option to ON,
when the frequency converter is the last station
on the segment.
Illustration 3.6 Option Mounted in FCP 106
3.6
Setting Address Switches
Set the address switches to give the option a unique ID.
Select an address range from 0–125 (factory setting 127)
according to Table 3.1.
Switch 8 7 6 5 4 3 2 1
Address
value
Not
used
+64 +32 +16 +8 +4 +2 +1
5 Not
used
OFF OFF OFF OFF ON OFF ON
35 Not
used
OFF ON OFF OFF OFF ON ON
82 Not
used
ON OFF ON OFF OFF ON OFF
Table 3.1 Settings for the Address Switches
Alternatively, assign a unique ID from parameter 9-18 Node
Address. For setting the address from parameter 9-18 Node
Address, ensure that all address switches are set to ON.
When the address is already set using address hardware
switches, the address value shown in parameter 9-18 Node
Address is read-only.
Installation
VLT
®
PROFIBUS DP MCA 101
8 Danfoss A/S © 07/2015 All rights reserved. MG33C602