State LED Description
Power on
Red:
Solid red
The interface is defect. Contact
Danfoss.
Green:
Flashing green
The interface is OK.
Baud rate search
Green:
Flashing green
Searching for the baud rate. Check
the connection to the master if
the interface stays in this state.
Wait parameterising
Green:
Long green
ash
Baud rate found - waiting for
parameters from the master.
Red:
Long red ash
Wrong parameters from the
master.
Wait conguration
Green:
Short green
ash
Parameters from master OK
waiting for conguration data.
Red:
Short red ash
Wrong conguration data from
the master.
Data exchange
Green:
Solid green
Data exchange between the
master and the frequency
converter is active.
Red:
Flashing red
Clear state. Warning 34, Fieldbus
fault is active and a bus reaction
in parameter 8-04 Control Word
Timeout Function is executed.
Table 4.2 Net Status
LED Description
No light O No PROFIBUS DP-V1 communication is active.
Green:
Short green ash DP-V1 communication from a master class 1
(PLC) is active.
Green:
Long green ash DP-V1 communication from a master class 2
(MCT 10, FDT) is active.
Green:
Solid green DP-V1 communication from a master class 1
and 2 is active.
Red:
Flashing red Internal fault.
Table 4.3 Module Status
4.2.2 No Communication with the
Frequency Converter
When there is no communication with the frequency
converter, check that:
The cabling is correct.
The red and green cables are connected to the
correct terminals as shown in Illustration 3.10.
The bus connection is terminated at both ends.
If not, terminate the bus connection with
termination resistors at the initial and nal nodes.
4.2.3 Warning 34 Fieldbus Fault Appears
Warning 34, Fieldbus fault is not only related to wiring.
Warning 34, Fieldbus fault appears when:
There is no master communication for 60 s after
power-up.
The master is in stop mode.
Master communication is not established, or is
incorrectly congured.
Wiring is incorrect.
Action:
Check the master mode and master
congu-
ration.
Check the wiring for correct master mode and
communication.
Troubleshooting Installation Guide
MG33C602 Danfoss A/S © 07/2015 All rights reserved. 15
4 4

Other manuals for Danfoss VLT PROFIBUS DP MCA 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT PROFIBUS DP MCA 101 and is the answer not in the manual?

Danfoss VLT PROFIBUS DP MCA 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT PROFIBUS DP MCA 101
CategoryMedia Converter
LanguageEnglish

Related product manuals