Page: 79
22. Appendix III.
22.1 ALARMS
Figure 28. Alarms Example
The figure above reflects how the two independent alarms are working. In this example alarm 1
is set to 12 ppm and alarm 2 is set to 15 ppm. Each alarm is set to an individual delay setting.
Once the oil content is higher than 12 ppm, alarm 1 LED will blink red until the alarm 1 delay is
exceeded. Then the alarm 1 contact will be in operation and alarm 1 LED will be continuously red
as long as the measurement is higher than 12 ppm. Once the measurement is below 12 ppm, the
alarm 1 contact will be out of operation and alarm 1 LED will be off.
Once the oil content is higher than 15 ppm, alarm 2 LED will blink red as long as alarm 2 delay is
exceeded. Then alarm 2 contact will be in operation and alarm 2 LED will be continuously red, as
long as the measurement is higher than 15 ppm. Once the measurement is below 15 ppm, alarm
2 contact will be out of operation and alarm 2 LED will be off.