Quick installation guide for RPI M15A M20A inverters
General safety instructions
1
DANGER
Risk of death by electrocution
Potentially fatal voltage is applied to the solar
inverter during operation. This potentially fatal
voltage is still present for 80 seconds after all
powersourceshavebeendisconnected.
Never open the solar inverter.
Always disconnect the solar inverter from
powerbeforeinstallation,opentheAC/DC
isolating switch and make sure neither can
beaccidentallyreconnected.
Wait at least 80 seconds until the capacitors
have discharged.
DANGER
Risk of death or serious injury from elec-
trocution
Potentiallyfatalvoltagemaybeappliedtothe
DC connections of the solar inverter. When light
is falling on solar modules, they immediately start
producing energy. They do so, even when the
sun is not shining.
Never disconnect the solar modules when the
solar inverter is powered.
First switch off the grid connection so that
the solar inverter cannot feed energy into the
grid.
Turn the DC disonnecting switch to position
OFF.
MakesuretheDCconnectionscannotbe
accidentally touched.
Thesolarinvertercanbesafelyandnormallyoperatedif
installed and used in accordance with this manual (see
IEC62109-5.3.3).DeltaEnergySystemsisnotresponsible
fordamageincurredbyfailuretoobservetheinstallationand
operatinginstructionsinthismanual.Forthisreason,besure
toobserveandfollowallinstructions!
Installationandcommissioningmayonlybeperformedby
qualiedelectriciansusingtheinstallationandcommission-
ing instructions found in this manual.
Thesolarinvertermustbedisconnectedfrompowerandthe
solarmodulesbeforeanyworkonitcanbeperformed.
The solar inverter has a high leakage current value. The
ground wire mustbeconnectedbeforecommissioning.
Do not remove any warning signs that the manufacturer has
installed on the solar inverter.
Improper handling of the solar inverter may result in physical
injuryanddamagetoproperty.Forthisreason,observeand
follow all general safety instructions and warnings.
Thesolarinvertercontainsnocomponentsthatmustbe
maintainedorrepairedbytheoperatororinstaller.Allrepairs
mustbeperformedbyDeltaEnergySystems.Openingthe
cover will void the warranty.
Donotdisconnectanycableswhenthesolarinverterispow-
ered due to risk of a fault arc.
To prevent lightning strikes, follow the relevant regulations
applicableinyourcountry.
Thesurfaceofthesolarinvertercanbecomeveryhotdur-
ing operation. Use safety gloves when working on the solar
inverter.
The
solarinverterisveryheavy.Thesolarinvertermustbe
liftedandcarriedbyatleasttwopeople.
OnlydevicesincompliancewithSELV(EN69050)maybe
connected to the RS485 and USB interfaces.
Allconnectionsmustbesufcientlyinsulatedinordertocom-
ply with the IP65 protection rating. Unused connections must
beclosedbyplacingcovercapsonthesolarinverter.