Quick installation guide for RPI M15A M20A inverters
Alwaysadheretothespecicregulationsapplicableinyourcoun-
try or region.
Alwaysadheretothespecicregulationsdenedbyyourgrid
operator.
For the safety of the user and for the security of your installation,
installrequiredsafetyandprotectiondevicesthatareapplicable
foryourinstallationenvironment(example:automaticcircuit
breakerand/orovercurrentprotectionequipment).
2
Usetheproperupstreamcircuitbreakertoprotecttheinverter:
Model Upstream Circuit Breaker
RPI-M15A 30 A
RPI-M20A 40 A
G N L1 L3L2
N
L1
L2
L3
PE
To solar inverter AC
plug
TheinverterisnotcapableoffeedinginDCresidualcurrentsdue
toitsdesign.ItfulllsthisrequirementinaccordancewithDIN
VDE0100-712.
ThepossibilitiesoffaultswereexaminedbyDeltawithouttak-
ingtheintegratedRCMU(residual-currentmonitoringunit)into
account. When examining these faults in terms of the current
validinstallationstandards,nodangerincombinationwithatype
Aupstreamresidual-currentdevice(RCD)canoccur.Therefore
faults that would otherwise require the use of a type B residual-
currentdeviceduetotheinvertercanbeexcluded.
The integrated all-pole sensitive RCMU provides additional
safety.RCDTypeAcanbeusedforthisinverter,accordingtothe
followingtable.
M15A M20A
Minimum tripping current of the RCD mA 100 100
NOTE
The value of the tripping current mainly depends
on the quality of the solar modules, the size of
thePVarrayandenvironmentalconditions(e.g.
humidity).
Important information regarding safety AC cable requirements
Use properly sized wires to connect to the correct poles (see
table)
AC connector Amphenol C16-3
Current rating 40 A
Min./max.cablediameter 11 ... 20 mm
Min./max.wirediameter 6 mm
2
Recommended torque for terminal
screws
0.7 Nm
TheACplugdeliveredwiththeinvertercanbeusedwithexible
coppercables.
Read and follow the instructions delivered with the AC plug.
Whencalculatingthecrosssectionofthecable,consider:
material used
thermal conditions
cablelength
type of installation
AC voltage drop
powerlossesincable
Alwaysfollowthesysteminstallationrequirementsdenedfor
yourcountry!
Australia/NewZealand:Alwaysfollowthesysteminstallation
requirementsdenedbyAS/NZS5033:2005regardingminimum
cablesectionsandprotectionsagainstoverheatingduetohigh
currents!
Grounding the inverter
TheinvertermustbegroundedviatheACconnector’sPEcon-
ductor. To do this, connect the PE conductor to the designated
terminal of the AC plug.
Markings on the inverter
Insomecountries,thefollowinglabelshavetobeappliedonthe
frontofeachmicroinverter.Pleasecheckapplicablenationaland
local standards and regulations.
WARNING
Dual Supply
Do not work on this equipment until it is isolated from
b oth mains and on site generation supplies
Isolate on-site Generating Unit(s) at … .
Isolate mains supply at…
Warning – Only persons authorised by the DNO may remove the main cut out fuse
Warning
Two sources of voltage present
-distributionnetwork
- photovoltaic panels
Isolatebothsourcesbefore
carrying out any work