6
Quick installation guide for RPI M15A M20A inverters
Planning the installation
5
ESC
ENT
ESC
ENT
> 50 cm
> 30 cm> 30 cm > 30 cm
> 20 cm
► Ensureadequateaircirculation.Hotairmustbeable
to dissipate upward. Keep enough space around each
inverter.
► Donotinstallinvertersdirectlyaboveoneanother.
Otherwise,theupperinverteriswarmedupbythe
lower one.
► Consider the operating temperature range (see sec-
tion“Technicaldata”).
When the operating temperature range is exceeded,
the solar inverter reduces the amount of power gener-
ated.
Ambient temperature and air circulation
Outdoor installations
► The solar inverter has protection
degree IP65 and can be installed
indoors or in protected outdoor
areas(thatmeansoutdoorbut
protectedbyaroofagainstdirect
sun,rainorsnow).
ESC
ENT
► Mount the solar inverter vertically.
Where to mount the inverter
?
?
?
?
► Mount the solar inverter so that the
LEDsanddisplaycanbeeasilyseen
andthatthebuttonscanbeoperated.
Make sure the reading angle and instal-
lationheightaresufcient.
► Always use the mounting plate
supplied with the solar inverter.
► Checkthatthewalliscapable
ofbearingtheheavyloadofthe
device.
► Use dowels and screws that are
suitableforthewallmaterialand
the heavy weight.
► Mount the solar inverter on a
vibration-freewalltoavoiddisrup-
tivevibrations.
► Possiblenoiseemissionscan
bedisruptivewhenthedeviceis
usedinlivingareasorinbuildings
with animals. Therefore, choose
your installation location carefully.
Mounting orientation
► The solar inverter is very heavy.
Thesolarinvertermustbe
liftedandcarriedbyatleasttwo
people.
43 kg