EasyManuals Logo
Home>Delta>DC Drives>VFD007EL43W

Delta VFD007EL43W User Manual

Delta VFD007EL43W
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
Chapter 4 Parameters
VFD-EL-W
4-85
Explanation of exception codes:
Exception code
Explanation
01
Illegal function code:
The function code received in the command message is not available for the AC
motor drive.
02
Illegal data address:
The data address received in the command message is not available for the AC
motor drive.
03
Illegal data value:
The data value received in the command message is not available for the AC
motor drive.
04
Slave device failure:
The AC motor drive is unable to perform the requested action.
10
Communication time-out:
If Pr.09.03 is not equal to 0.0, and Pr.09.02 = 02, and there is no communication
on the bus during the time-out detection period (Pr.09.03), the keypad displays
“cE10”.
7. Communication program for a PC:
The following is a simple example of how to write a communication program for Modbus ASCII mode on a
PC in the C language.
#include<stdio.h>
#include<dos.h>
#include<conio.h>
#include<process.h>
#define PORT 0x03F8 /* the address of COM1 */
/* the address offset value relative to COM1 */
#define THR 0x0000
#define RDR 0x0000
#define BRDL 0x0000
#define IER 0x0001
#define BRDH 0x0001
#define LCR 0x0003
#define MCR 0x0004
#define LSR 0x0005
#define MSR 0x0006
unsigned char rdat[60];
/* read 2 data from address 2102H of AC drive with address 1 */
unsigned char tdat[60]={':','0','1','0','3','2','1','0',’2', '0','0','0','2','D','7','\r','\n'};
void main(){
int i;
outportb(PORT+MCR,0x08); /* interrupt enable */
outportb(PORT+IER,0x01); /* interrupt as data in */
outportb(PORT+LCR,(inportb(PORT+LCR) | 0x80));
/* the BRDL/BRDH can be access as LCR.b7==1 */
outportb(PORT+BRDL,12); /* set baudrate=9600, 12=115200/9600*/
outportb(PORT+BRDH,0x00);
outportb(PORT+LCR,0x06); /* set protocol, <7,N,2>=06H, <7,E,1>=1AH, <7,O,1>=0AH,
<8,N,2>=07H, <8,E,1>=1BH, <8,O,1>=0BH */
for(i=0;i<=16;i++){
while(!(inportb(PORT+LSR) & 0x20)); /* wait until THR empty */
outportb(PORT+THR,tdat[i]); /* send data to THR */ }
i=0;
while(!kbhit()){
if(inportb(PORT+LSR) & 0x01){ /* b0==1, read data ready */
rdat[i++]=inportb(PORT+RDR); /* read data form RDR */
} } }
09.05 Reserved

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD007EL43W and is the answer not in the manual?

Delta VFD007EL43W Specifications

General IconGeneral
BrandDelta
ModelVFD007EL43W
CategoryDC Drives
LanguageEnglish

Related product manuals