Chapter 4 Parameters
VFD-EL-W
4-34
2 Linear acceleration and auto-deceleration.
3 Auto-acceleration and auto-deceleration (set by load)
4 Auto-acceleration and auto-deceleration (set by Acceleration/Deceleration Time
setting)
With auto-acceleration and auto-deceleration it is possible to reduce vibration and shocks during starting and
stopping the load.
During auto-acceleration, the torque is automatically measured and the drive accelerates to the set frequency
with the shortest acceleration time and the smoothest starting current.
During auto-deceleration, the drive measures the regenerative energy and the motor is stopped smoothly with
the shortest deceleration time.
When this parameter is set to 4, the actual acceleration/deceleration time are equal to or greater than
Pr.01.09–Pr.01.12.
Auto-acceleration and auto-deceleration makes the complicated processes of tuning unnecessary. It makes
operation efficient and saves energy by acceleration without stalling and deceleration without using the brake
resistor.
In applications with the brake resistor or brake unit, it is not recommended to use auto-deceleration.
01.17
Acceleration S-Curve Unit: 0.1 / 0.01
01.18
Deceleration S-Curve Unit: 0.1 / 0.01
Default: 0.0 / 0.00
Settings 0.0 S-curve disabled
0.110.0/0.0110.00
S-curve enabled (10.0/10.00 is the smoothest)
Ensure smooth acceleration and deceleration using an S-curve.
0: Disables the S-curve function.
0.1–10.0/0.01–10.00: Enables the S-curve function.
Setting the parameter to 0.1/0.01 gives the shortest S-curve and setting the parameter to 10.0/10.00 gives the
longest and smoothest S-curve.
The following diagram shows that the original setting of the Acceleration and Deceleration Time is only for
reference when you enable the S-curve. The actual acceleration and deceleration time depends on the
selected S-curve (0.1 to 10.0). Pr.01.17 must be smaller than Pr.01.09 or Pr.01.11; Pr.01.18 must be smaller
than Pr.01.10 or Pr.01.12. Otherwise, the S-curve is invalid.
The total acceleration time = Pr.01.09 + Pr.01.17 or Pr.01.11 + Pr.01.17
The total deceleration time = Pr.01.10 + Pr.01.18 or Pr.01.12 + Pr.01.18
3
1
2
4
1
3
4
2
1 2
3
4
Disable S curve
Enable S curve
Acceleration/deceleration Characteristics
01.20
Simple Positioning Stop Frequency 0 Unit: 0.01
Settings 0.00–400.00Hz Default: 0.0
0
01.21
Simple Positioning Stop Frequency 1 Unit: 0.01
Settings 0.00–400.00Hz Default: 5.00
01.22
Simple Positioning Stop Frequency 2 Unit: 0.01
Settings 0.00–400.00Hz Default: 10.00