Chapter 12 Description of Parameter SettingsME300
12.1-07-9
Fan Cooling Control
Default: 3
Settings 0: Fan always ON
1: Fan is OFF after the AC motor drive stops for one minute.
2: When the AC motor drive runs, the fan is ON. When the AC motor drive
stops, the fan is OFF.
3: Fan turns ON when the temperature reaches around 60
o
C
5: Fan turns ON/OFF when the AC motor drive runs/stops and stops at zero
speed.
Use this parameter to control the fan.
0: Fan runs immediately when the drive power is turned ON.
1: Fan runs when AC motor drive runs. One minute after AC motor drive stops, the fan is OFF.
2: Fan runs when AC motor drive runs and stops immediately when AC motor drive stops.
3: When temperature of the IGBT or capacitance is higher than 60
o
C, the fan runs.
When the temperature of the IGBT and capacitance both are lower than 40
o
C, the fan stops.
Deceleration of Emergency or Forced Stop
Default: 0
Settings 0: Coast to stop
1: Stop by the first deceleration time
2: Stop by the second deceleration time
3: Stop by the third deceleration time
4: Stop by the fourth deceleration time
5: System deceleration
6: Automatic deceleration
When the multi-function input terminal is set to EF input (setting 10) or forced to stop (setting 18)
and the terminal contact is ON, the drive stops according to the setting of this parameter.