01 Basic Parameters
Pr. Explanation Settings Default
01-00
Maximum operation
frequency of motor 1
0.00–599.00 Hz
60.00/
50.00
01-01
Output frequency of
motor 1
0.00–599.00 Hz
60.00/
50.00
01-02 Output voltage of motor 1
115V / 230V series: 0.0–255.0 V
460V series: 0.0–510.0 V
220.0
440.0
01-03
Mid-point frequency 1 of
motor 1
0.00–599.00 Hz 3.00
01-04
Mid-point voltage 1 of
motor 1
115V / 230V series: 0.0–240.0 V
460V series: 0.0–480.0 V
11.0
22.0
01-05
Mid-point frequency 2 of
motor 1
0.00–599.00 Hz 1.5
01-06
Mid-point voltage 2 of
motor 1
115V / 230V series: 0.0–240.0 V
460V series: 0.0–480.0 V
5.0
10.0
01-07
Minimum output
frequency of motor 1
0.00–599.00 Hz 0.50
01-08
Minimum output voltage of
motor 1
115V / 230V series: 0.0–240.0 V
460V series: 0.0–480.0 V
1.0
2.0
01-09 Start-up frequency 0.00–599.00 Hz 0.50
01-10
Output frequency
upper limit
0.00–599.00 Hz 599.00
01-11
Output frequency
lower limit
0.00–599.00 Hz 0.00
01-12 Acceleration time 1
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0
01-13 Deceleration time 1
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0
01-14 Acceleration time 2
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0
01-15 Deceleration time 2
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0
01-16 Acceleration time 3
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0
01-17 Deceleration time 3
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0
01-18 Acceleration time 4
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
10.00
10.0