Chapter 12 Description of Parameter SettingsME300
12.1-03-15
Settings Functions Descriptions
16 Vq-axis voltage command 250 V (500 V) = 100%
17 Vd-axis voltage command 250 V (500 V) = 100%
21 RS-485 analog output For InnerCOM analog output
23 Constant voltage output
Pr.03-32 controls the voltage output level.
0–100.00% of Pr.03-32 corresponds to 0–10 V of AFM.
Analog Output Gain (AFM)
Default: 100.0
Settings 0–500.0%
Adjusts the voltage level outputted to the analog meter from the analog signal (Pr.03-20) output
terminal AFM of the drive.
Analog Output in REV Direction (AFM)
Default: 0
Settings 0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
Analog output direction selection
AFM Output Bias
Default: 0.00
Settings -100.00–100.00%
Example 1: AFM 0–10 V is set to the output frequency, the output equation is
27-03 10V 21-03 )
00-01
FrequencyOutput
(10V ×+××
Example 2: AFM 0–20 mA is set to the output frequency, the output equation is
27-0320mA 21-03 )
00-01
FrequencyOutput
(20mA ×+××
Example 3: AFM 4–20 mA is set to the output frequency, the output equation is
27-0316mA 21-03 )
00-01
FrequencyOutput
(16mA4mA ×+××+
This parameter sets the corresponding voltage for the analog output 0.
Freq. Freq. Freq.
Pr.03-22=0
Pr.03-22=1 Pr.03-22=2