Chapter 12 Description of Parameter SettingsME300
12.1-05-2
Stator Resistance (Rs) for Induction Motor 1
Rotor Resistance (Rr) for Induction Motor 1
Default: #.###
Settings 0.000–65.535 Ω
Magnetizing Inductance (Lm) for Induction Motor 1
Stator Inductance (Lx) for Induction Motor 1
Default: #.#
Settings 0.0–6553.5 mH
Full-load Current for Induction Motor 2 (A)
Unit: Ampere
Default: #.##
Settings 10–120% of the drive’s rated current
Set this value according to the rated current of the motor as indicated on the motor nameplate.
The default is 90% of the drive’s rated current.
Example: The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A.
The setting range is 2.5–30 A. (25 × 10 % = 2.5 A and 25 × 120 % = 30 A)
Rated Power for Induction Motor 2 (kW)
Default: #.##
Settings 0.00–655.35 kW
Sets the rated power for motor 2. The default is the drive’s power value.
Rated Speed for Induction Motor 2 (rpm)
Default: 1710
Settings 0–65535 rpm
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
Sets the rated speed for the motor as indicated on the motor nameplate.
Number of Poles for Induction Motor 2
Default: 4
Settings 2–20
Sets the number of poles for the motor (must be an even number).
Set up Pr.01-35 and Pr.05-15 before setting up Pr.05-04 to make sure the motor operates
normally.
No-load Current for Induction Motor 2 (A)
Unit: Ampere
Default: #.##
Settings 0.00–Pr.05-13 default
The default is 40% of the motor's rated current.