Chapter 11 Summary of Parameter SettingsMS300
240
07 Special Parameters
Software Brake Chopper
Action Level
115V / 230V models: 350.0–450.0 V
DC
460V models: 700.0–900.0 V
DC
575V models: 875.0–1000.0 V
DC
DC Brake Time at Start-Up
DC Brake Frequency at
STOP
Restart after Momentary
Power Loss
0: Stop operation
1: Speed tracking by the speed before the power loss
2: Speed tracking by the minimum output frequency
Allowed Power Loss
Duration
Current Limit of Speed
Tracking
Restart after Fault Action
0: Stop operation
1: Speed tracking by current speed
2: Speed tracking by minimum output frequency
Number of Times of Restart
after Fault
Speed Tracking during
Start-Up
0: Disable
1: Speed tracking by the maximum output frequency
2: Speed tracking by the motor frequency at start-up
3: Speed tracking by the minimum output frequency
0: Disable
1: dEb with auto-acceleration / auto-deceleration, the
drive does not output the frequency after the power is
restored.
2: dEb with auto-acceleration / auto-deceleration, the
drive outputs the frequency after the power is restored.
3: dEb low-voltage control, then the drive’s voltage
increases to 350 V
DC
/ 700 V
DC
and ramps to stop
after low frequency
4: dEb high-voltage control of 350 V
DC
/ 700 V
DC
, and the
drive ramps to stop
Dwell Time at Acceleration