Chapter 11 Summary of Parameter SettingsMS300
257
IGBT Temperature at
Malfunction 6
Refer to fault record Pr.06-17–Pr.06-22
Refer to fault record Pr.06-17–Pr.06-22
Refer to fault record Pr.06-17–Pr.06-22
Refer to fault record Pr.06-17–Pr.06-22
Over-Torque Detection
Selection (Motor 3)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
Over-Torque Detection
Level (Motor 3)
10–250%
(100% corresponds to the rated current of the drive)
Over-Torque Detection
Time (Motor 3)
Over-Torque Detection
Selection (Motor 4)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant speed
operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
Over-Torque Detection
Level (Motor 4)
10–250%
(100% corresponds the rated current of the drive)
Over-Torque Detection
Time (Motor 4)
Electronic Thermal Relay
Selection 3 (Motor 3)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with the fan on the shaft)
2: Disable
Electronic Thermal Relay
Action Time 3 (Motor 3)
Electronic Thermal Relay
Selection 4 (Motor 4)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with the fan on the shaft)
2: Disable
Electronic Thermal Relay
Action Time 4 (Motor 4)